MICROTEX OPzV cells are maintenance free Gel lead - acid type with long life. In applications with high requirements of operational safety and bridging times of 1h to more than 10h the MICROTEX OPzV is the right choice.
MICROTEX Stationary OPzV Cells are used in Telecommunication Sectors, for Emergency Lighting, for Microwave Radio and Solar Photovoltaic Systems and also in Power Generating Plants. |
| Types, Capacity, Dimensions and Mass |
Type |
C10
25°C |
C8
25°C |
C5
25°C |
C3
25°C |
C1
25°C |
Ri
(1) |
Ik
(2) |
Length |
Width |
Height
(max.) |
Mass
|
lead Mass |
|
Ah |
Ah |
Ah |
Ah |
Ah |
mW |
kA |
mm |
mm |
mm |
kg |
kg |
|
|
|
|
|
|
|
|
|
|
|
|
|
4 OPzV 200 |
238 |
232 |
211 |
188 |
140 |
1.20 |
1.70 |
105 |
208 |
420 |
19,5 |
13 |
5 OPzV 250 |
298 |
291 |
263 |
235 |
174 |
0.96 |
2.15 |
126 |
208 |
420 |
23,5 |
15 |
6 OPzV 300 |
356 |
349 |
319 |
281 |
209 |
0.80 |
2.57 |
147 |
208 |
420 |
28 |
19 |
5 OPzV 350 |
427 |
416 |
371 |
324 |
234 |
0.71 |
2.88 |
126 |
208 |
535 |
31 |
21 |
6 OPzV 420 |
512 |
499 |
448 |
389 |
281 |
0.60 |
3.46 |
147 |
208 |
535 |
36,5 |
24 |
7 OPzV 490 |
597 |
583 |
520 |
454 |
329 |
0.51 |
4.04 |
168 |
208 |
535 |
42 |
27 |
6 OPzV 600 |
729 |
710 |
633 |
562 |
402 |
0.45 |
4.58 |
147 |
208 |
710 |
50 |
34 |
8 OPzV 800 |
972 |
948 |
845 |
751 |
537 |
0.34 |
6.10 |
215 |
193 |
710 |
68 |
45 |
10 OPzV 1000 |
1215 |
1187 |
1056 |
936 |
670 |
0.27 |
7.63 |
215 |
235 |
710 |
82 |
55 |
12 OPzV 1200 |
1463 |
1417 |
1267 |
1125 |
804 |
0.23 |
9.15 |
215 |
277 |
710 |
97 |
65 |
12 OPzV 1500 |
1669 |
1648 |
1437 |
1239 |
893 |
0.24 |
8.58 |
215 |
277 |
855 |
120 |
80 |
16 OPzV 2000 |
2225 |
2200 |
1916 |
1650 |
1191 |
0.18 |
11.4 |
215 |
400 |
815 |
160 |
107 |
20 OPzV 2500 |
2781 |
2752 |
2395 |
2064 |
1488 |
0.14 |
14.3 |
215 |
490 |
815 |
200 |
133 |
24 OPzV 3000 |
3337 |
3304 |
2874 |
2475 |
1786 |
0.12 |
17.1 |
215 |
580 |
815 |
240 |
160 |
| 1), 2) internal resistance and short - circuit - current from IEC 60 896-21 |
| Note : 1) The electrical characteristics are nominal indicative value and can vary within +/- 5.0%. |
| (2) Dimension can vary within +/- 2.0m |
| (3) Weight figures can vary within +/- 5.0% |
|
|
|
|
4 OPzV 200 to 6 OPzV 600 |
8 OPzV 800 to 12 OPzV 1500 |
16 OPzV 2000 |
20 OPzV 2500 to 24 OPzV 3000 |
|
Positive electrode - |
Tubular plate with a polyester gauntlet and High pressure-die cast spine grids in a corrosion-resistant PbCaSn alloy |
|
Negative electrode - |
Pasted grid-plate in a PbCaSn alloy with long-life expander |
|
Separation - |
Micro porous separator. |
|
Electrolyte - |
Sulphuric acid with a density of 1,26 kg/l, fixed as GEL by fumed silica |
|
Container - |
ABS |
|
Lid - |
ABS |
|
Valve - |
Valve with flame arrestor. Opening pressure approx. 100 mbar. Closing pressure approx. 50 mbar. |
|
Pole-bushing - |
100% gas- and electrolyte-tight, sliding, plastic coated kind of pole with M10 brass insertion |
|
Connectors - |
Solid flat copper connectors |
|
Connectors Screw - |
M10, steel with a spring and flat washer |
|
Protection - |
Connectors and fasteners are covered with Plastics shroud |
|
Horizontal Operation- |
Possible |
|
IU - Characteristic - |
Imax without limitation |
|
|
U = 2,25V/cell +/- 1%, between 10°C and 45°C |
|
|
∆U/∆T = -0,003 V/K |
|
Float current - |
20 – 30 mA/100Ah |
|
Boost charge - |
U = 2,35 to 2,40V/cell, time limited |
|
Charging time up to 90% - |
6h with1,5*I10 initial current,2.23 V/cell, 80% C3 discharged |
| Discharge Characteristics |
|
Reference temperature - |
25°C |
|
Initial capacity - |
100% |
|
Depth of discharge(DOD)- |
normally up to 80% |
|
Deep discharges - |
More than 80% DOD or discharges beyond final discharge |
|
|
voltages (based on discharge rate) have to be avoided |
|
Every 6 months - |
Check battery voltage, pilot cell voltage and temperature |
|
Every 12 months - |
Record battery voltage, cell voltages and temperatures |
|
Operational life - |
> 20 years in standby float operation, 27C |
|
Maintenance-free - |
No topping-up water during operational life |
|
IEC 60 896-2 cycles - |
>1800 |
|
Self-discharge - |
Approx. 2% per month at 25°C |
|
Recovery after discharge - |
Very Good |
|
Operational temperature - |
-20°C to 45°C, recommended 10°C to 35°C, short time 45°C to 55°C |
|
Standard - |
DIN 40 742 part 1 |
|
Tests according - |
IEC 60 896 – 21, -22 |
|
Safety standard, ventilation |
DIN EN 50 272-2 |
|