MICROTEX OPzS cells belong to the most enduring lead acid batteries. They are suitable for stand - by operations as well as for capacitive loads. They perfectly meet requirements for bridging times between 1h and more than 10h.
MICROTEX Stationary OPzS Cells are used in Telecommunication Sectors, for Emergency Lighting and Microwave Radio Systems and also in Power Generating Plants. |
| Types, Capacity, Dimensions and Mass |
Type |
C10
20°C |
C5
20°C |
C3
20°C |
C1
20°C |
C8
25°C |
Ri
1) |
Ik
2) |
Length |
Width |
Height
(max.) |
Mass
3) |
Mass
4) |
Lead mass |
|
Ah |
Ah |
Ah |
Ah |
Ah |
mW |
kA |
mm |
mm |
mm |
Kg |
Kg |
Kg |
Ue
V/cell |
1.80 |
1.77 |
1.75 |
1.67 |
1.75 |
|
|
|
|
|
|
|
|
4 OPzS 200 |
210 |
175 |
156 |
114 |
205 |
0,95 |
2.16 |
105 |
208 |
420 |
12.2 |
17.2 |
11.9 |
5 OPzS 250 |
270 |
220 |
195 |
143 |
255 |
0,76 |
2.70 |
126 |
208 |
420 |
14.6 |
20.8 |
14.3 |
6 OPzS 300 |
320 |
262 |
234 |
170 |
304 |
0,63 |
3.24 |
147 |
208 |
420 |
17.2 |
24.3 |
16.6 |
5 OPzS 350 |
400 |
336 |
282 |
205 |
378 |
0,70 |
2.90 |
126 |
208 |
535 |
18.9 |
26.9 |
18.5 |
6 OPzS 420 |
490 |
400 |
339 |
245 |
452 |
0,58 |
3.48 |
147 |
208 |
535 |
22.2 |
31.5 |
22.2 |
7 OPzS 490 |
570 |
470 |
396 |
285 |
526 |
0,50 |
4.06 |
168 |
208 |
535 |
25.2 |
36.1 |
26.0 |
6 OPzS 600 |
670 |
560 |
474 |
330 |
657 |
0,47 |
4.32 |
147 |
208 |
710 |
31.9 |
44.8 |
34.0 |
8 OPzS 800 |
890 |
740 |
633 |
440 |
880 |
0,35 |
5.76 |
215 |
193 |
710 |
44.2 |
61.3 |
43.5 |
10 OPzS 1000 |
1120 |
930 |
789 |
550 |
1096 |
0,28 |
7.20 |
215 |
235 |
710 |
52.3 |
74.5 |
53.0 |
12 OPzS 1200 |
1340 |
1100 |
948 |
660 |
1312 |
0,23 |
8.64 |
215 |
277 |
710 |
62.1 |
88.0 |
62.0 |
12 OPzS 1500 |
1690 |
1400 |
1200 |
820 |
1672 |
0,23 |
9.18 |
215 |
277 |
855 |
80.4 |
114.3 |
74.0 |
16 OPzS 2000 |
2250 |
1850 |
1600 |
1100 |
2232 |
0,17 |
12.24 |
215 |
400 |
815 |
102.5 |
151.5 |
116.0 |
20 OPzS 2500 |
2810 |
2300 |
2000 |
1375 |
2792 |
0,14 |
15.30 |
215 |
490 |
815 |
129.8 |
193.0 |
141.0 |
24 OPzS 3000 |
3380 |
2800 |
2400 |
1640 |
3344 |
0,11 |
18.36 |
215 |
580 |
815 |
159.4 |
234.5 |
170.0 |
| 1,2) Iinternal resistance and short - circuit - current from IEC 60896-11 |
| 3) Dry-Charged 4) Filled and Charged |
| Note : 1) The electrical characteristics are nominal indicative value and can vary within +/- 5.0% |
| (2) Dimension can vary within +/- 2.0mm |
| (3) Weight figures can vary within +/- 5.0% |
|
|
|
|
4 OPzS 200 to 6 OPzS 600 |
8 OPzS 800 to 12 OPzS 1500 |
16 OPzS 2000 |
20 OPzS 2500 to 24 OPzS 3000 |
|
Positive electrode - |
Tubular plate with a polyester gauntlet and die cast spine in a corrosion-resistant PbSbSnSe - alloy |
|
Negative electrode - |
Pasted grid plate in low antimony alloy with long-life expander material |
|
Separation - |
Micro porous separator. |
|
Electrolyte - |
Sulphuric acid with a density of 1,24 kg/l. |
|
Container - |
High impact, transparent SAN (Styrene-Acrylo-Nitrile) |
|
Lid - |
SAN in dark grey colour |
|
Plugs - |
Microporous ceramic top plugs |
|
Pole - bushing - |
100% gas- and electrolyte-tight, sliding, plastic coated with M10 brass insertion |
|
Connectors - |
Solid copper flat connectors |
|
Fastener - |
M10, steel bolt with spring and flat washer |
|
Protection - |
Plastics shrouds cover the connectors and fastener |
|
IU - Characteristic - |
Imax without limitation |
|
|
U = 2,23 V/cell +/- 1%, between 10°C and 55°C |
|
|
∆U/∆T = -0,003 V/K |
|
Float current - |
15mA/100Ah, increasing to 30mA/100Ah at the end of life |
|
Boost charge - |
U = 2,35 to 2,40V/cell, time limited |
|
Charging time up to 88% - |
6h with1,5*I10 initial current,2.23 V/cell, 80% C3 discharged |
| Discharge Characteristics |
|
Reference temperature - |
27°C |
|
Initial capacity - |
100% |
|
Depth of discharge(DOD)- |
normally up to 80% |
|
Deep discharges - |
More than 80% DOD or discharges beyond final discharge |
|
|
voltages (based on discharge rate) have to be avoided |
|
Every 6 months - |
Check battery voltage, pilot cell voltage and temperature |
|
Every 12 months - |
Record battery voltage, cell voltages and temperatures |
|
Operational life - |
15+ years in stand-by float operation |
|
Water refilling interval - |
More than 3 years at 20°C |
|
IEC 896-11 cycles - |
>1500 |
|
Self-discharge - |
Approx. 3% per month at 20°C |
|
Operational temperature - |
-20°C to 55°C, recommended 10°C to 30°C |
|
Standard - |
DIN 40 736 part 1 |
|
Tests according - |
IEC 60 896 - 11 |
|
Safety standard, ventilation |
DIN EN 50 272-2 |
|